Skip to content

Modbus TCP

All gateways equipped with ethernet port support Modbus TCP in master mode.

Features

  • Supports communication with multiple Modbus TCP slave devices.
  • Enables remote monitoring and control of devices over an IP network.
  • Compatible with all features supported for Modbus RTU.

Configuration

  1. Ensure the gateway is connected to the local network via Ethernet.
  2. Assign a static IP address or configure DHCP for the gateway.
  3. Use the rayleighconnect™ cloud platform to configure Modbus TCP settings:
    • Select the device model from the dropdown list of supported models.
    • Provide the IP address of the Modbus TCP slave device.
    • The default Modbus TCP port is 502.
    • The platform automatically configures the registers based on the selected model.

For a list of supported models, see Meters and Sensors.

Use Cases

  • Monitoring industrial equipment such as PLCs, sensors, and actuators.
  • Collecting data from energy meters and other Modbus-enabled devices.
  • Integrating Modbus TCP devices into centralized energy management systems.

Limitations

  • The number of slave devices is shared between Modbus RTU and Modbus TCP.
  • Network latency may affect real-time data acquisition.

For more information on configuring Ethernet settings, see Ethernet.