Modbus TCP
All gateways equipped with ethernet port support Modbus TCP in master mode.
Features
- Supports communication with multiple Modbus TCP slave devices.
- Enables remote monitoring and control of devices over an IP network.
- Compatible with all features supported for Modbus RTU.
Configuration
- Ensure the gateway is connected to the local network via Ethernet.
- Assign a static IP address or configure DHCP for the gateway.
- Use the rayleighconnect™ cloud platform to configure Modbus TCP settings:
- Select the device model from the dropdown list of supported models.
- Provide the IP address of the Modbus TCP slave device.
- The default Modbus TCP port is
502
. - The platform automatically configures the registers based on the selected model.
For a list of supported models, see Meters and Sensors.
Use Cases
- Monitoring industrial equipment such as PLCs, sensors, and actuators.
- Collecting data from energy meters and other Modbus-enabled devices.
- Integrating Modbus TCP devices into centralized energy management systems.
Limitations
- The number of slave devices is shared between Modbus RTU and Modbus TCP.
- Network latency may affect real-time data acquisition.
For more information on configuring Ethernet settings, see Ethernet.