Skip to content

Default Configuration Reference

This document lists the factory default configuration of the RI‑EC-series and RI-EX-series, including network, credentials, enabled services, and other key settings.

Default Configuration Table

Cellular (4G LTE-M / 2G)

Parameter Default Value Security Impact / Recommendation
APN m2msims Change for your SIM/provider
SMS Access Enabled within 10 minutes of boot Disable after initial setup;
Configure credentials to disable boot behaviour;
Use phone numbers whitelist feature to limit access

Ethernet

Parameter Default Value Security Impact / Recommendation
DHCP Enabled Disable after intial setup;
Use only if needed; static IP recommended
Static IP 192.168.0.15 Change to match your secure network
Netmask 255.255.255.0 Review for network segmentation
Gateway 192.168.0.1 Review for correct routing
DNS 8.8.8.8 Use trusted DNS servers

RS-458 Modbus RTU

Parameter Default Value Security Impact / Recommendation
RS-485 Enabled (Modbus RTU) Setup addressing and review access
RS-485
Baudrate
9600 8N1 Change if required
RS-485
Response Timeout
1000 ms Change if required
RS-485
Minimum Delay
50 ms Change if required

Interfaces

Parameter Default Value Security Impact / Recommendation
USB Access Enabled Physical access required; Located under top lid.
Extension Port
Baudrate
115200 8E1 Change if required

Cloud Platform communication

Parameter Default Value Security Impact / Recommendation
Cloud Host ht3.uxeon.com
c4.rxcx.net
m1.rxcx.net
Review and restrict as needed
Cloud Port 90 Review and restrict as needed
Cloud Host
(recovery)
ht0.uxeon.com Review and restrict as needed
Cloud Port
(recovery)
99 Review and restrict as needed
Communication Interval 60 seconds Change if required

For more information and guidance see Firewall setup guide